Grounding:

Whenever flammable or combustible liquids are transferred from one container to another, both containers shall be effectively bonded and grounded. This practice prevents electrical discharge from the accumulation of static charge because of the transfer process.

Electrical:

Electrical Wiring:

Electrical wiring and equipment shall conform to the provisions of the National Electrical Code (NFPA 70). Electrical wiring located in spray areas must be rigid metal conduit, Type MI cable, or in metal boxes or fitting containing no taps, splices or terminal connections. There are alternative electrical wiring in options when the location is adjacent to (rather than inside) a spray area (NFPA 33).

Electrical Equipment:

Electrical equipment outside of, but within 20 feet horizontally and 10 feet vertically, of any spraying area and not separated from it by partitions extending at least to the boundary of the Division 2 location shall be of non-spark producing design. This equipment shall also conform to the provisions of NFPA 70, for Class I or Class I, Division 2 locations as applicable. If spraying operations are confined to an enclosed spray booth or room, the space adjacent to the booth or room shall be considered non-hazardous except for the space within three feet in all directions from any opening in the booth or room.

Grounding:

All metal parts of spray booths and exhaust ducts conveying flammable or combustible liquids or aerated combustible solids shall be electrically grounded.

208